ADPI-BX-200 Primary Current Injection Test Set

Latest News »
ADTC-950 INTELLIGENT DRY BLOCK TEMPERATURE CALIBRATOR ADFC-1000 plus High-Precision Multifunctional Process Calibrator ADPC-800 Series process calibrator ADTC-750 Series Temperature Calibrator

General information about ADPI-BX-200 Primary Current Injection Test Set:
ADPI-BX-200 Primary Current Injection Test Set, is mainly used for testing current transformer, motor protector, air switch, switch cabinet, circuit breaker, protection screen and etc.
Features:
PVC panel, simple and neat.
With low power, big capacity autotransformer regulator and converter inside.
Quick connects, lock design, good current-through capability.
Built-in quick plug with high safety, to ensure reliable cable connection and improve test efficiency.
Current range can be changed, easy to read.
Engineering plastics box, dust-proof and waterproof, IP67 class.
Portable design, suitable for on-site testing.
Damping design, to ensure reliable transportation
Zero start function to prevent the test objects from damage caused by high current impulse. The equipment only can be started from zero.
Impulse selection function. The required current can be output directly without zero protection function when making quick-break testing for circuit breaker.
Accurate measurement. LCD digital indicator to display output current and voltage. The resolution of output current is 1A .
Output 0-50A AC current, suitable for over current quick break testing of secondary protection.
Action time can be tested synchronously.
More calibrations can be series connected at the same time to improve working efficiency .
Directly display primary current and secondary current, convenient for CT/PT turn ratios calibration test. (Optional)

  • PDF
  • specifications
There are no photos
false

Technical Specification of the device:
Power supply: AC 220V 50Hz.
Output power: 3kVA.
Output current: 500A in series,1000A in parallel.
Output voltage: 6V in series, 3V in parallel.
Current can be adjusted smoothly and continuously. The accuracy is 1.0%.
Output current is standard sine wave, waveform distortion is less than 5%.
Secondary injection current: 50A
Output current: RMS continuous adjustable.
The action time of test object can be tested, the lock action time is also can be recorded at the same time.
Test range: 0.001S-999.999S, resolution 1ms, error: 0.005%, range: ±2digits
Duty Cycle: 5mins ON, 10mins OFF.

There are no video